Fatality #4 for Metal/Nonmetal Mining 2009

On April 7, 2009, a 36 – year old supervisor with 15 years of experience was fatally injured at a sand and gravel dredging operation. The victim was attempting to connect the 4160 volt cable for the dredge to load side terminals in the electrical panel when he came into contact with energized 4160 volt line side terminals.

Best Practices

Before YOU perform electrical work:

  • Be trained and knowledgeable in the task.
  • Be trained on all the electrical test and safety equipment necessary to safely test and ground the circuit being worked on.
  • Use properly rated Personal Protective Equipment including Arc Flash Protection such as a hood, gloves, shirt, and pants.
  • Positively identify the circuit on which work is to be conducted.
  • De-energize power and ensure that the circuit is visibly open.
  • Place YOUR lock and tag on the disconnecting device.
  • Verify the circuit is de-energized by testing for voltage using properly rated test equipment.
  • Ensure all electrical components in the cabinet are de-energized.
  • Ground ALL phase conductors to the equipment grounding medium with grounding equipment that is properly rated.

Click here for: MSHA Investigation Report(pdf), Overview(powerpoint), Overview(pdf)